How to measure AI inference energy

Eight steps that turn "how much energy does this model use?" into a figure someone else can check.

Article · Reviewed 3 November 2026

The eight steps

  1. Fix the task set. Choose versioned tasks that represent the real workload.
  2. State the quality gate. Decide what counts as a passing answer; only passing tasks count.
  3. Declare the meter point. Chip, board, rack or facility. Comparisons must match.
  4. Use a proper analyzer. At M1 to M3, a SPEC-accepted power analyzer controlled through PTDaemon, with clocks synchronized by NTP (Tschand et al., MLPerf Power).
  5. Run a ranging pass. Find peak voltage and current, then fix the ranges for the measured run.
  6. Measure long enough. At least 60 seconds per window; loop short tasks.
  7. Close the ledger. Check that the accounts balance with the closure rule.
  8. Report fully. Decision Yield with meter point, accuracy, label and grade.

Why on-board counters are not enough

Counters on chips and boards are convenient but can drift from true power. JL-26 counts them as Measured only after they are validated against an analyzer on the same system; otherwise they are Estimated.

Why per-query figures disagree

Published "energy per query" estimates vary widely mainly because they use different boundaries, tasks and quality bars. Some count only the accelerator; others include the host, networking or the facility. The benchmark comparison shows what each benchmark includes.

Questions

Can we measure in the cloud?

Often only with on-board telemetry, which is Estimated unless validated. A rack-level measurement at M3 needs physical access or the provider's metered data.

Sources

  1. Tschand et al., MLPerf Power